Error codes for LG industrial air conditioners
Indoor unit:
- 01 - air temperature sensor short-circuited or open circuit;
- 02 - evaporator temperature sensor short-circuited or open circuit;
- 03 - poor connection of the indoor unit with a wired control panel;
- 04 - error of the drainage pump (pump) or float condensate level sensor;
- 05 - error in the interblock connection of the external and internal blocks;
- 06 - outdoor unit temperature sensor short-circuited or open circuit;
- 07 - the internal blocks of the multisystem are included in different operating modes;
- HL - same error as 04, float sensor open;
- CL - a child’s lock is installed; to turn it on, press Timer & Min Buttons for 3 seconds;
- Po - jet cool mode is set, press jet cool to exit
External unit:
- 21 - compressor overload current;
- 22 - compressor current more than 14 A;
- 23 - DC voltage below 140 V; (not the supply voltage, but after the conversion module)
- 24 - error on high / low pressure, pressure sensors are open;
- 25 - supply voltage above / below the normal value;
- 26 - DC Compressor Position;
- 27 - error PSC (reactor, inductor);
- 28 - DC Link High Volts;
- 32 - High temperature discharge pipe (INV);
- 33 - High temperature discharge pipe (Cons.);
- 40 - short circuit CT;
- 41 - temperature sensor D-Pipe closed / disconnected (INV);
- 44 - the outdoor temperature sensor is closed / torn;
- 45 - capacitor temperature sensor closed / torn;
- 46 - the sensor on the suction tube is closed / torn off;
- 47 - D-pipe sensor closed / broken;
- 48 - D-pipe sensor and air temperature sensor missing / broken;
- 51 - combined power overload;
- 52 - connection error (main micom-sub micom);
- 53 - connection error (indoor-outdoor units);
- 54 - for systems with 3-phase power supply, incorrect phase sequence, change phase;
- 60 - EEPROM error (internal non-volatile memory)
- 61 - high temperature condenser tube (condenser)
- 62 - high temperature of the radiator (most likely the radiator is cooling the power module of the inverter)
- 63 - low condenser temperature
- 65 - radiator temperature sensor short-circuited
- 67 - blocked external BLDC (brushless DC motor) fan
- 105 - no communication between the main control board and the fan control board
Error codes for all LG wall-mounted air conditioners, including the Art Cool series
- C1 or CH1 - the internal air temperature sensor is short-circuited or open in the circuit;
- C2 or CH2 - evaporator temperature sensor short-circuited or open circuit;
- C4 or CH4 - the condenser temperature sensor is short-circuited or open in the circuit;
- C5 or CH5 - connection between the external and internal units;
- C6 or CH6 - current in the inverter module circuit is exceeded;
- C7 or CH7 - compressor current is exceeded;
- C8 or CH8 - the fan of the indoor unit does not rotate;
- C9 or CH9 - the fan of the external unit does not rotate;
- C10 or CH-10 - the thermistor for monitoring the temperature of the compressor housing of the split system is faulty (open or short circuit)
- CA - discharge temperature above 130 0С;
- CC - error EEPROM (internal non-volatile memory);
- CD - error in the inverter module;
- CE
- Po - the system is in energy-saving mode, there is no error;
- Lo - the system is in test mode, there is no error;
If there is no error code, and the LED indicators on the panel blink, you need to download the full version of the error code, there is also a graph of the temperature sensor resistance versus temperature.
All Error/ Fault Codes for LG Air Conditioner’s
LG Air Conditioner’s: All Error/ Fault Codes (DTC)
Download: LG Air Conditioner’s All Error Codes.pdf (338.3 KB)